CDU-M

CDU-M

Commercial refrigeration

Intermediate solution to cool in negative or positive from 2kW at -35°C to 5.6kW at +5°C

Evaporating temperature-35 °C-30 °C-10 °C-5 °C+5 °C
Cooling capacity2.0 kW2.16 kW4.33 kW4.87 kW5.6 kW
Electric power input2.11 kW2.13 kW2.62 kW2.76 kW2.78 kW

Operation temperatureEvaporating (Min/Max)-35 ~ +5 °C
Ambient (Min/Max)-25 ~ +43 °C
Dimensions*Height x Width x Depth1.300 x 1.100 x 281 mm
Weight 107 kg
Noise pressure level (1)1 meter away49 dB(A)
CompressorTypeInverter Hermetic Scroll
Speed35 ~ 80 Hz
Heat ExchangerTypeAluminium microchannel
RefrigerantType / GWPR744 CO2 / 1
Power supplyPhases /Voltage/ FrequencySingle-phased / 230 / 50 ou 60 (-/V/Hz)
CommunicationStandardModbus
PEDCategory1
Maximum working pressure (MWP)High pressure side14 MPa
Low pressure side9 Mpa
(1) Conditions : T° Ambient +32°C, Compressor Speed 80hz * without pipe cover